Control Algorithm

Execution Cycle

The coordinator runs every 60 seconds and performs:

  1. PID Update (per zone)
  2. Historical State Query (per zone)
  3. Zone Decision (per zone)
  4. Pump & Heat Request Aggregation
  5. Safety Lockout
  6. Boiler Mode Management

PID Controller

The PID controller calculates a duty cycle (0-100%) from the temperature error (setpoint minus current temperature).

Calculation:

  • Proportional term: Kp × error (immediate response to temperature deviation)
  • Integral term: Ki × accumulated error over time (eliminates steady-state error)
  • Derivative term: Kd × rate of error change (damping, typically disabled for slow hydronic systems)

Anti-windup protection: The integral term is clamped between configurable limits (default 0-100%) to prevent unbounded accumulation when the system cannot reach setpoint.

Output clamping: The final duty cycle is clamped to 0-100%.

PID Integration Pausing

To prevent integral windup during periods when heating is blocked or irrelevant, the PID controller's update() method is skipped (integration paused) when any of the following conditions are true:

Condition Reason
Temperature unavailable Cannot calculate meaningful error without current temperature
Controller mode ≠ heat PID control only applies in heat mode
Zone disabled Disabled zones don't participate in heating
Window open (above threshold) Heating blocked, would cause integral windup

When paused:

  • The integral term is frozen at its current value
  • The duty cycle is maintained at its last calculated value
  • The error term is still updated (for UI display purposes)

This prevents the common problem of integral windup where the integral term accumulates while the room temperature is unstable after a window opening, which would cause overshoot when normal control resumes.

Time Windows

Window Duration Calculation
Observation Period 2 hours (default) Aligned to midnight (00:00, 02:00, 04:00...)
Valve Position Estimation 7 minutes (default) valve_open_time + valve_close_time (physical position estimation)

Heat Accounting

Heat accounting tracks how much of its quota each zone has consumed during the observation period, with optional supply-temperature normalization to adjust for actual heating conditions.

Key concepts:

  • used_duration accumulates only when flow=True (valve confirmed open)
  • When a supply temperature sensor is configured, accumulation is weighted by the supply coefficient
  • At period boundaries, all zones reset to fresh quota

See Heat Accounting for detailed documentation.

Zone Decision Tree

The zone evaluation follows a priority-based decision tree:

  1. Absolute DHW priority: If dhw_priority is absolute and DHW is charging (or the dhw_recovery_time hold-off has not expired), every circuit is driven closed. This overrides all the steps below, including the already-on and end-of-period-freeze paths, because the hazard it guards against is hydraulic rather than thermal — see dhw_priority.

  2. Flush circuit priority: If flush is enabled and DHW has recently ended with no regular circuits currently running, flush circuits turn on to capture latent heat from the boiler.

  3. End-of-period freeze: When less than min_run_time remains in the observation period, valve positions are frozen to prevent unnecessary cycling at period boundaries.

  4. Quota-based scheduling: For zones that haven't met their quota:

    • If valve is already on: stay on (commands are re-sent to prevent relay timeout)
    • If estimated wall clock runtime is less than min_run_time: stay off (not worth a short run). When a supply coefficient is available, remaining quota is converted to estimated wall clock time (capped at remaining quota so coefficients above 100% never shorten the estimate): estimated_runtime = max(remaining_quota, remaining_quota / (supply_coefficient / 100)). Without a supply sensor, remaining quota is compared directly.
    • If dhw_priority is partial (the default), DHW is active and this is a regular circuit currently off: stay off. Circuits already running are left alone; parallel skips this check entirely.
    • Otherwise: turn on
  5. Quota met: For zones that have met their quota:

    • If valve is on: turn off
    • If valve is off: stay off

Note: Window blocking affects PID integration (pausing accumulation), not valve control directly. Valves follow quota-based scheduling regardless of window state. Absolute DHW priority is the one exception that does close valves, since no amount of PID pausing keeps DHW-temperature water out of the floor.

Note: PID integration continues normally during a DHW block. The room temperature reading stays valid and the room really is losing heat, so the integral builds and the zone catches up once the block clears.

Note: Quota is preserved rather than compensated, but not instantly. used_duration accrues while flow is true, and flow is derived from the estimated valve position, which ramps down over valve_close_time after the block commands the valve shut. A zone therefore keeps consuming quota for roughly the first 15% of valve_close_time (about 30 s at the default 210 s) before flow drops below the 0.85 threshold. That is deliberate: during that window the circuit is receiving cylinder-temperature water, so it is being charged for heat it genuinely got. If DHW spans an observation-period boundary the unused remainder is dropped, which the PID integral self-corrects over the next period.

Heat Request Logic

The controller computes a single heat request signal from all zones with active flow:

  • Only zones with flow=True (valve confirmed fully open) are considered
  • A zone contributes to the heat request when its remaining_duration exceeds the closing_warning_duration (zone won't close imminently)
  • If any qualifying zone needs heat, the boiler heat request is enabled
  • While a DHW block is in force both the heat request and the pump request are suppressed outright. Thermal actuators take minutes to close, so a circuit still reports flow immediately after DHW asserts; without this the controller would ask the boiler to fire mid-charge and keep an independent circulation pump pushing cylinder-temperature water through the closing circuit.

Boiler Summer Mode Management

When a summer mode entity is configured and the controller is in automatic mode:

  • If heat is requested and summer mode is not "winter": switch to "winter" (enables heating circuit)
  • If no heat is requested and summer mode is not "summer": switch to "summer" (disables heating circuit, saves energy)